CVE Database · CVE-2023-5768
CVSS v3.1
5.9
EPSS
0.41%
Published
Dec 4, 2023
Modified
Nov 21, 2024
Public PoC / Exploit
All weaponized →No public PoC or exploit code indexed for this CVE.
Links to public security research (Exploit-DB, Nuclei, Trickest, GitHub) for defensive use only.
Description
A vulnerability exists in the HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Incomplete or wrong received APDU frame layout may cause blocking on link layer. Error reason was an endless blocking when reading incoming frames on link layer with wrong length information of APDU or delayed reception of data octets. Only communication link of affected HCI IEC 60870-5-104 is blocked. If attack sequence stops the communication to the previously attacked link gets normal again.
CVSS Vector
CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:HWeaknesses (CWE)
Affected Products (32)
References (2)